In order to ensure an
even distribution of hot water to the radiators in a system you'll
need to 'balance the system'. Often the radiators near to the
boiler/pump would tend to be warmer than the radiators further away,
balancing the system will even out the flow of the hot water.
To do this we use the lockshield valve which is normally hidden
under a push on cover at one end of the radiator. Adjusting these
valves will regulate the flow of water to the radiator. By partially
closing the valves, flow to the radiators nearest the boiler can be
more limited than to those further away. To reduce the water
temperature at the outlet pipe, the lock shield is closed; to
increase the temperature the valve is opened up.
The idea is to get temperature drop across each radiator to be about
12 °C (20 °F). The easiest way to measure the temperature drop
across the radiators is to use a set of radiator thermometers. These
clamp-on thermometers have springs which hook around the inlet and
outlet pipes of a radiator. They can be found at any DIY story.
Before you begin make sure the system is turned off and let the
water cool down.
Open the lock shield valve and the control valve using an adjustable
spanner closed small. This is the valve you use to turn the radiator
on and off.
Fit the radiator thermometers to the Inlet and Outlet pipes of the
radiator which is nearest to the boiler and switch the heating back
on.
Close the lockshield valve on the first radiator to almost closed,
as the temperature of the systems comes up, gradually open up the
valve until the temperature difference between the two radiator
thermometers is about 12°C (20°F)
Move the thermometers to the next radiator away from the boiler.
Close down the lockshield valve and adjust it until the temperature
difference increases to about 12°C (the temperature difference will
probably start at less than 12 degrees as both valves are fully
open).
If you repeat this for all of them in order, you should have a
balanced system so that all radiators heat up efficiently.
Once the radiators in a system have been balanced, the valves should
not need to be adjusted again unless the radiators or the pipes are
changed.
About the Author:
D. Benjamin Castonguay is the owner of iapsales.com
LLC - a family business specializing in
HVAC products. We are distributors of
Qmark Heaters,
electric
tankless water heaters, bathroom
heaters, patio heaters,
electric heaters,
portable air
conditioners &
electric towel warmers. Shop on line at
www.heateroutlet.com for these great home improvement products.
Iapsales.com LLC was established in 2003 and is the sister company to Innovative Air Products located in historical Exeter, NH. We are a 2nd generation manufacturers’ rep firm dedicated to providing residential & commercial heating, ventilation and air-conditioning equipment. We offer a great selection online at the lowest prices anywhere. We can also be found on Facebook, Twitter and YouTube.